Item |
Specification |
Power supply |
Rated voltage of power supply |
Three-phase 340V-10% to 460V+10% 50-60Hz ± 5%; voltage unbalance rate: <3% |
Output |
Maximum output voltage |
The maximum output voltage is the same as the input power voltage. |
Rated output current |
Continuous output of 100% rated current |
Maximum overload current |
G model: 150% rated current for 60s P model: 120% rated current for 60s (2kHz carrier; please derate for carriers above this level) |
Basic control |
Driving mode |
V/F control (VVF); Speed sensorless vector control (SVC) Speed sensor vector control (FVC) |
Input mode |
Frequency (speed) input, torque input |
Start and stop control mode |
Keyboard, control terminal (two-line control and three-line control),communication |
Frequency control range |
0.00~600.00Hz/0.0~3000.0Hz |
Input frequency resolution |
Digital input: 0.01Hz Analog input: 0.1% of maximum frequency |
Speed control range |
1:50 (VVF), 1:200 (SVC), 1:1000 (FVC) |
Speed control accuracy |
±0.5% (VVF), ±0.2% (SVC), ±0.02% (FVC) |
Acceleration and deceleration time |
0.01s~600.00s/0.1s~6000.0s/1s~60000s |
Voltage/frequency characteristics |
Rated output voltage 20%~100% adjustable, reference frequency 1Hz~600Hz/3000Hz adjustable |
Torque boost |
Fixed torque boost curve, any V/F curve optional |
Starting torque |
150%/3Hz (VVF), 150%/0.25Hz (SVC), 180%/0Hz (FVC) |
Torque control accuracy |
±5% rated torque (SVC), ±3% rated torque (FVC) |
Self-adjustment of output voltage |
When the input voltage changes, the output voltage will basically remain unchanged. |
Automatic current limit |
Output current is automatically limited to avoid frequent overcurrent trips. |
DC braking |
Braking frequency: 0.01 to maximum frequency Braking time: 0~30S Braking current: 0%~150% rated current |
Signal input source |
Communication, multi-speed, analog, high-speed pulse, etc. |
Input and output |
Reference power supply |
10.5V±0.5V/20mA |
Terminal control power |
24V/200mA |
Digital input terminal |
7 (standard configuration X1~X7) + 3 (extension card X8~X10)-channel digital multi-function inputs: X7 can be used as a high-speed pulse input terminal (F02.06 = 35/38/40); X1~X6 and X8~X10, totally 9 terminals that can only serve as ordinary digital input terminals |
Analog input terminal |
3 (standard configuration AI1 ~ AI3) + 1 (extension card AI4)-channel analog input: 1-channel AI1: support 0 ~ 10V or -10~ 10V, optional for selection by using function code F02.62; 2-channel AI2/AI3: support 0 ~ 10V or 0~ 20mA or 4~ 20mA, optional for selection by using function code F02.63 and F02.64 is optional; 1-channel AI4: support 0 ~ 10V or -10~ 10V, optional for selection by using function code F02.65 |
Digital output terminal |
2 (standard Y1/Y2) open-collector multi-function outputs + 2 (R1: EA/EB/EC and R2: RA/RB/RC) relay multi-function outputs + 2 (extension card) (R3: RA3/RC3 and R4: RA4/RC4) relay multi-function outputs Maximum output current of the collector: 50 mA; Relay contact capacity 250VAC/3A or 30VDC/1A, with EA-EC and RA-RC normally open, EB-EC and RB-RC normally closed; RA3-RC3, RA4-RC4 normally open |
Analog output terminal |
2-channel (M1/M2) multi-function analog output terminals to output 0~10V or 0~20mA or 4~20mA, optional for selection by using function codes F03.34 and F03.35 |
Operation panel |
LCD display |
The LCD digital tube displays relevant information about the inverter. |
Parameter copying |
Parameter settings of the inverter can be uploaded and downloaded for fast parameter copying. |
Protection |
Protective Function |
Short circuit, overcurrent, overvoltage, undervoltage, phase loss, overload, overheat, overspeed, load loss, external fault, etc. |
Use conditions |
Location |
Indoor, at an altitude of less than 1 km, free of dust, corrosive gases and direct sunlight |
Applicable environment |
-10ºC to +50ºC, derating by 5% per 1ºC increase above 40ºC, 20% to 90%RH (non-condensing) |
Vibration |
Less than 0.5g |
Storage environment |
-40ºC~+70ºC |
Installation method |
Wall-mounted, floor-standing electrical control cabinet, through-wall |
Protection level |
Protection level |
Standard IP21/IP20 (remove the plastic cover at the top of the plastic case) |
Cooling method |
Cooling method |
Forced air cooling |